Default properties of trend logs

When a new trend log object is created (either manually, by the BACnet quality check or when creating surrogate BACnet objects), some properties will be initialized with default values.

Default properties of trend logs

Property

Default value

Stop_When_Full

false

Activated

true

Notification_Class

192

Notify_Type

1

Client_COV_Increment

Depends on the unit of the referenced object. See table below.

Buffer_Size

100

Notification_Threshold

90

Default values of Client_COV_Increment and Logging_Type depending on the unit of the referenced object

Unit

Default Client_COV_Increment

Default Logging_Type

%

2

1

% obs./mtr.

2

1

% rf

5

1

%/s

2

1

°C

0.5

1

A

0.5

1

a

0.1

1

bar

0.1

1

cd

5

1

cd/m²

5

1

cycle/min

1

1

d

0.1

1

g(H₂O)/kg dry air

5

1

h

0.25

1

hPa

10

1

Hz

0.5

1

J

100

1

J/kg·K

10

1

K

0.5

1

K/h

0.5

1

K/min

0.5

1

kJ

10

1

kJ/kg

10

1

kJ/kg dry air

10

1

km/h

1

1

kPa

1

1

kV

0.5

1

kVA

1

1

kvar

1

1

kW

1

1

kWh/m²

10

1

l/h

10

1

l/min

10

1

l/s

1

1

m/s

1

1

m³/h

10

1

m³/s

0.5

1

mA

1

1

mbar

1

1

min

5

1

MJ

1

1

MJ/kg dry air

10

1

MJ/m²

10

1

mo

0.1

1

MV

0.5

1

MVA

0.1

1

Mvar

0.1

1

MW

0.1

1

Pa

10

1

pf

0.1

1

ppb

50

1

ppm

50

1

s

60

1

S

5

1

V

0.5

1

VA

10

1

var

10

1

W

10

1

W/m²·K

1

1

wk

0.1

1

1

1

Units not listed above have a default Client_COV_Increment of 1 and a default Logging_Type of 0.